Flat connectors

Above, modeling of a low voltage 5000 A, three phase with neutral. 4 copper conductors by phase. Section of one conductor: 160 x 5 mm

* Study no° 1 : the 4 neutral conductors are positioned to the centre of the casing

* Study no° 2 : The 4 neutral conductors are positioned on the right of the casing

With this modeling, it is possible to control the induced current into the neutral conductors. If the neutral is placed to the centre of the busduct, the induced current is 10 times lower, regarding the solution with the neutral on one side of the busduct. Moreover, the subtransmission between the conductors of one same phase is much more homogenous.

Study of a 2000A one-pole efficient system on one resistive load. Modeling of the the power subtransmossion in one conductor 200 x 6 mm.

Study of a one-pole 2000A efficient system on one resistive load. Modeling of the subtransmission of the magnetic flux in the air, loosened by a conductor 200 x 6 mm.

Study of a 2000 A one pole efficient system, on a resistive load. Board of measure of the induction loosened by a one bar 200 x 6 mm.

 